Heating load in Cape Girardeau

A home in Cape Girardeau has to be heated against a design temperature of −11.8 °C. That figure is measured, not modelled: it is the 1st percentile of daily minimum temperature over 15 years at Cairo Regional Airport, 38 km away.

Design temperature −11.8 °C
Heating degree days 1,605
Coldest month Jan
Coldest night on record −24.6 °C

How many kilowatts

Heating power needed at the design temperature, in kilowatts, for a detached house. Pick the row that matches the building.

Construction Detached Semi-detached Terraced Top-floor flat Mid-floor flat Ground-floor flat
Uninsulated, single glazed 20.5 kW 18.0 kW 16.0 kW 17.5 kW 8.5 kW 10.4 kW
Unfilled cavity, early double glazing 13.9 kW 12.0 kW 10.4 kW 10.2 kW 6.2 kW 7.7 kW
Insulated to 1980s standards 7.9 kW 7.1 kW 6.5 kW 6.1 kW 4.4 kW 5.6 kW
Modern, roughly 1995-2010 4.9 kW 4.4 kW 4.1 kW 3.9 kW 3.0 kW 3.6 kW
Current building regulations 3.7 kW 3.4 kW 3.2 kW 3.1 kW 2.3 kW 2.8 kW
Passive house 2.2 kW 2.0 kW 1.8 kW 1.7 kW 1.2 kW 1.6 kW

Where the heat goes

For a 120 m2 detached house of this construction, at the design temperature.

Element W Share
Walls 2,612 33%
Roof 763 10%
Ground floor 515 7%
Windows 1,488 19%
Thermal bridges 437 6%
Ventilation and draughts 2,108 27%
Heating load 7,924 7.9 kW

Calculate it for your own home

The climate half of this is measured. The building half is yours to supply.

Heating load

Monthly mean temperature

JanFebMarAprMayJunJulAugSepOctNovDec
°C 2.4 4.1 9.9 15.4 20.8 25.6 26.3 25.0 21.3 15.1 8.8 4.5

Where these numbers come from