Heating load in Timaru

A home in Timaru has to be heated against a design temperature of −4.7 °C. That figure is measured, not modelled: it is the 1st percentile of daily minimum temperature over 24 years at Timaru Aerodrome Aws, 11 km away.

Design temperature −4.7 °C
Heating degree days 2,054
Coldest month Jul
Coldest night on record −7.8 °C

How many kilowatts

Heating power needed at the design temperature, in kilowatts, for a detached house. Pick the row that matches the building.

Construction Detached Semi-detached Terraced Top-floor flat Mid-floor flat Ground-floor flat
Uninsulated, single glazed 15.9 kW 14.0 kW 12.4 kW 13.6 kW 6.6 kW 8.1 kW
Unfilled cavity, early double glazing 10.8 kW 9.3 kW 8.1 kW 7.9 kW 4.8 kW 6.0 kW
Insulated to 1980s standards 6.2 kW 5.5 kW 5.0 kW 4.7 kW 3.4 kW 4.4 kW
Modern, roughly 1995-2010 3.8 kW 3.5 kW 3.2 kW 3.1 kW 2.3 kW 2.8 kW
Current building regulations 2.9 kW 2.7 kW 2.5 kW 2.4 kW 1.8 kW 2.2 kW
Passive house 1.7 kW 1.5 kW 1.4 kW 1.4 kW 0.9 kW 1.2 kW

Where the heat goes

For a 120 m2 detached house of this construction, at the design temperature.

Element W Share
Walls 2,029 33%
Roof 593 10%
Ground floor 400 7%
Windows 1,156 19%
Thermal bridges 340 6%
Ventilation and draughts 1,638 27%
Heating load 6,155 6.2 kW

Calculate it for your own home

The climate half of this is measured. The building half is yours to supply.

Heating load

Monthly mean temperature

JanFebMarAprMayJunJulAugSepOctNovDec
°C 15.5 15.3 13.7 10.5 7.9 5.1 4.6 6.2 8.5 10.4 12.2 14.3