Heating load in Orléans

A home in Orléans has to be heated against a design temperature of −29.0 °C. That figure is measured, not modelled: it is the 1st percentile of daily minimum temperature over 30 years at Gatineau, 9 km away.

Design temperature −29.0 °C
Heating degree days 3,640
Coldest month Jan
Coldest night on record −37.0 °C

How many kilowatts

Heating power needed at the design temperature, in kilowatts, for a detached house. Pick the row that matches the building.

Construction Detached Semi-detached Terraced Top-floor flat Mid-floor flat Ground-floor flat
Uninsulated, single glazed 31.6 kW 27.7 kW 24.6 kW 27.0 kW 13.1 kW 16.1 kW
Unfilled cavity, early double glazing 21.4 kW 18.4 kW 16.1 kW 15.7 kW 9.5 kW 11.9 kW
Insulated to 1980s standards 12.2 kW 11.0 kW 10.0 kW 9.4 kW 6.8 kW 8.6 kW
Modern, roughly 1995-2010 7.5 kW 6.9 kW 6.3 kW 6.1 kW 4.6 kW 5.5 kW
Current building regulations 5.8 kW 5.3 kW 4.9 kW 4.7 kW 3.6 kW 4.3 kW
Passive house 3.4 kW 3.1 kW 2.8 kW 2.7 kW 1.8 kW 2.4 kW

Where the heat goes

For a 120 m2 detached house of this construction, at the design temperature.

Element W Share
Walls 4,025 33%
Roof 1,176 10%
Ground floor 794 7%
Windows 2,293 19%
Thermal bridges 674 6%
Ventilation and draughts 3,249 27%
Heating load 12,211 12.2 kW

Calculate it for your own home

The climate half of this is measured. The building half is yours to supply.

Heating load

Monthly mean temperature

JanFebMarAprMayJunJulAugSepOctNovDec
°C −9.9 −8.1 −1.9 6.7 14.9 19.9 22.4 21.0 16.3 8.9 1.9 −5.4