Heating load in Busselton

A home in Busselton has to be heated against a design temperature of 1.4 °C. That figure is measured, not modelled: it is the 1st percentile of daily minimum temperature over 23 years at Busselton Aero, 6 km away.

Design temperature 1.4 °C
Heating degree days 538
Coldest month Jul
Coldest night on record −0.8 °C

How many kilowatts

Heating power needed at the design temperature, in kilowatts, for a detached house. Pick the row that matches the building.

Construction Detached Semi-detached Terraced Top-floor flat Mid-floor flat Ground-floor flat
Uninsulated, single glazed 12.0 kW 10.5 kW 9.3 kW 10.2 kW 5.0 kW 6.1 kW
Unfilled cavity, early double glazing 8.1 kW 7.0 kW 6.1 kW 5.9 kW 3.6 kW 4.5 kW
Insulated to 1980s standards 4.6 kW 4.2 kW 3.8 kW 3.6 kW 2.6 kW 3.3 kW
Modern, roughly 1995-2010 2.9 kW 2.6 kW 2.4 kW 2.3 kW 1.7 kW 2.1 kW
Current building regulations 2.2 kW 2.0 kW 1.9 kW 1.8 kW 1.3 kW 1.6 kW
Passive house 1.3 kW 1.2 kW 1.1 kW 1.0 kW 0.7 kW 0.9 kW

Where the heat goes

For a 120 m2 detached house of this construction, at the design temperature.

Element W Share
Walls 1,528 33%
Roof 446 10%
Ground floor 301 7%
Windows 870 19%
Thermal bridges 256 6%
Ventilation and draughts 1,233 27%
Heating load 4,635 4.6 kW

Calculate it for your own home

The climate half of this is measured. The building half is yours to supply.

Heating load

Monthly mean temperature

JanFebMarAprMayJunJulAugSepOctNovDec
°C 21.5 21.7 20.1 17.2 14.3 12.5 11.6 12.0 12.8 14.7 17.5 19.8